1 / 5
Model No. : | YJY22 |
---|---|
Brand Name : | HUAYUAN YONGTONG |
Type : | Insulated |
Beijing, Beijing, China
Descripción del Producto
1. NORMAS DE APPLICALBE
El cable debe diseñarse, fabricarse y probarse de acuerdo con las normas internacionales de la siguiente manera:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Cable Standard |
|
IEC 60502-1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60332-3-24 |
Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C |
2. ESTRUCTURA DE LOS CABLES PARA CABLE 0.6 / 1KV
CU / PVC / PVC / STA / FR-PVC 0.6 / 1 kV 2 × 50
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
8.1 |
2.XLPE insulation |
1.0 |
10.1 |
3. Filler |
/ |
20.8 |
4. Wrapping tape |
0.2 |
21.4 |
5. PVC Inner sheath |
1.2 |
23.8 |
6. Galvanized steel tape armor |
0.2 |
24.6 |
7. FR-PVC Outer sheath |
1.8 |
28.2 |
CU / PVC / PVC / STA / FR-PVC 0.6 / 1 kV 2 × 25
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
5.9 |
2.XLPE insulation |
0.9 |
7.7 |
3. Filler |
/ |
15.8 |
4. Wrapping tape |
0.2 |
16.4 |
5. PVC Inner sheath |
1.2 |
18.8 |
6. Galvanized steel tape armor |
0.2 |
19.6 |
7. FR-PVC Outer sheath |
1.8 |
23.2 |
CU / PVC / PVC / STA / FR-PVC 0.6 / 1 kV 2 × 6
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
3.06 |
2.XLPE insulation |
0.7 |
4.5 |
3. Filler |
/ |
9.0 |
4. Wrapping tape |
0.2 |
9.6 |
5. PVC Inner sheath |
1.2 |
12.0 |
6. Galvanized steel tape armor |
0.2 |
12.8 |
7. FR-PVC Outer sheath |
1.8 |
16.4 |
3. REQUISITOS DE PRUEBA PARA CABLES DE ENERGÍA LV
La prueba del cable debe realizarse de acuerdo con el estándar aplicable de los cables de potencia de 0.6 / 1kV. Los siguientes elementos de prueba se llevarán a cabo de acuerdo con las normas pertinentes de IEC.
No. |
Test item |
Routine tests |
|
1 |
measurement of the electrical resistance of conductors |
2 |
Voltage test |
Sample tests |
|
1 |
conductor examination |
2 |
check of dimensions |
3 |
Hot set test for XLPE insulation |
4. INFORMACIÓN DE EMBALAJE PARA CABLES DE ALIMENTACIÓN DE 0.6 / 1KV
Los cables deben estar enrollados en tambores de acero y madera. La marca indeleble se imprimirá en la superficie de la brida del tambor de acuerdo con los requisitos del cliente.
Fábrica y equipo
Paquete
Honor
1.Three Core Copper Conductor 2.Five Core Copper Conductor 3.1kv Cable 4. Low Voltage Power Cable 5. Cable resistente al fuego 6. Mica Tape Insulated Cable 7.Fire-proof Cable 8.Flame Retardant Cables
Beijing, Beijing, China
Envíe su consulta a este proveedor