1 / 5
Model No. : | NH-YJV |
---|---|
Brand Name : | HUAYUAN YONGTONG |
Type : | Insulated |
Beijing, Beijing, China
Descripción del Producto
1. REQUISITOS DE PRUEBA PARA CABLES DE ENERGÍA LV
La prueba del cable debe realizarse de acuerdo con el estándar aplicable de los cables de potencia de 0.6 / 1kV. Los siguientes elementos de prueba se llevarán a cabo de acuerdo con las normas pertinentes de IEC.
No. |
Test item |
Routine tests |
|
1 |
measurement of the electrical resistance of conductors |
2 |
Voltage test |
Sample tests |
|
1 |
conductor examination |
2 |
check of dimensions |
3 |
Hot set test for XLPE insulation |
2. ESTÁNDARES DE APPLICALBE
El cable que ofrece TBEA se diseñará, fabricará y probará de acuerdo con las normas internacionales de la siguiente manera:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Cable Standard |
|
IEC 60502-1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60332-3-24 |
Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C |
El cable de cobre contra incendios, el cable resistente al fuego, el cable a prueba de fuego, el cable ignífugo aislado y los cables ignífugos pueden usarse en lugares muy difíciles, especialmente en el aeropuerto y la escuela.
3. ESTRUCTURA DE CABLES PARA CABLE 0.6 / 1KV
CU / PVC / PVC / STA / FR-PVC 0.6 / 1 kV 3 × 25 + 1 × 16
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
5.9 |
2. mica tape |
0.14 |
6.9 |
3.XLPE insulation |
0.9 |
8.7 |
4. Filler |
/ |
20.1 |
5. Wrapping tape |
0.2 |
20.7 |
6. PVC Inner sheath |
1.2 |
23.1 |
7. Galvanized steel tape armor |
0.2 |
23.9 |
8. FR-PVC Outer sheath |
1.8 |
27.5 |
Cable FR de CU / PVC / PVC / STA / FR-PVC 0.6 / 1kV 3 × 16 + 1 × 10
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
4.8 |
2. mica tape |
0.14 |
5.8 |
3.XLPE insulation |
0.7 |
7.2 |
4. Filler |
/ |
17.0 |
5. Wrapping tape |
0.2 |
17.6 |
6. PVC Inner sheath |
1.2 |
20.0 |
7. Galvanized steel tape armor |
0.2 |
20.8 |
8. FR-PVC Outer sheath |
1.8 |
24.4 |
CU / PVC / PVC / STA / FR-PVC FR-Cable 0.6 / 1kV 3 × 6 + 1 × 4
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
3.06 |
2. mica tape |
0.14 |
4.1 |
3.XLPE insulation |
0.7 |
5.5 |
4. Filler |
/ |
12.8 |
5. Wrapping tape |
0.2 |
13.4 |
6. PVC Inner sheath |
1.2 |
15.6 |
7. Galvanized steel tape armor |
0.2 |
15.4 |
8. FR-PVC Outer sheath |
1.8 |
19.0 |
4. INFORMACIÓN DE EMBALAJE PARA CABLES DE ALIMENTACIÓN DE 0.6 / 1KV
Los cables deben estar enrollados en tambores de acero y madera. La marca indeleble se imprimirá en la superficie de la brida del tambor de acuerdo con los requisitos del cliente.
Paquete:
Honor
Beijing, Beijing, China
Envíe su consulta a este proveedor